Electrical Fittings and Accessories in Buildings

Electrical Fittings and Accessories in Buildings

Electrical fittings and accessories are essential components of a building’s electrical installation. They provide convenient points for controlling lighting, connecting appliances, supporting electrical connections, routing wiring and protecting electrical circuits. Their selection and placement influence electrical safety, usability, maintenance, interior design and coordination with other building services.

For architects, electrical fittings are not merely small items shown on an electrical layout. Their location affects furniture arrangements, wall elevations, ceiling design, accessibility, equipment operation and the appearance of interior spaces. Good coordination between architecture, electrical engineering and interior design helps ensure that fittings are functional, safe and visually integrated.

This guide explains the principal types of electrical fittings and accessories, their functions, common building applications, selection criteria and architectural planning considerations, with reference to Indian electrical standards and safety regulations.

What Are Electrical Fittings and Accessories?

Electrical fittings and accessories are components installed as part of, or in connection with, an electrical installation to provide switching, connection, lighting, mounting, cable management and other functions.

Examples include switches, socket-outlets, plugs, lamp holders, luminaires, ceiling roses, junction boxes, mounting boxes and conduit fittings. Protective devices such as circuit breakers and residual-current devices serve related but distinct safety functions.

The exact meaning of fitting and accessory can vary between standards, manufacturers and everyday usage. For building-design purposes, the terms are often used collectively to describe the smaller components that enable an electrical installation to operate conveniently and safely.

Why Are Electrical Fittings Important?

Electrical fittings contribute to a building’s:

  • Functionality: providing convenient controls and connection points for lighting and equipment.
  • Safety: supporting appropriate enclosure, insulation, earthing and circuit protection arrangements.
  • Architectural quality: coordinating with wall finishes, ceilings, joinery and interior colour schemes.
  • Accessibility: placing controls and outlets where intended users can reach and operate them.
  • Maintainability: allowing inspection, replacement and servicing without unnecessary damage to finishes.
  • Adaptability: accommodating changes in furniture, equipment and patterns of building use.

The suitability of any fitting depends on its intended use, electrical rating, environmental conditions, compatibility with the installation and applicable requirements.

Types of Electrical Fittings and Accessories

Electrical fittings can be grouped by their principal function. This classification helps architecture students understand the components shown on electrical layouts and helps designers coordinate their positions with the building plan.

CategoryExamplesPrincipal function
Switching and controlOne-way switches, two-way switches, dimmersControl lighting and compatible equipment
ConnectionSocket-outlets, plugs, connectorsConnect electrical appliances to a supply
LightingLuminaires, lamp holders, ceiling rosesSupport, connect or distribute light
Wiring and cable managementConduits, bends, junction boxes, cable glandsRoute and protect wiring
Mounting and enclosureMounting boxes, cover plates, electrical enclosuresSecure components and protect connections
Circuit protectionMCBs, RCDs, RCBOs, surge protective devicesProtect against specified electrical faults or surges
Earthing and bondingProtective conductors, earthing terminals, bonding connectionsSupport protective measures against electric shock
Specialist controlOccupancy sensors, timers, smart switchesAutomate or remotely control selected functions

These categories overlap. For example, a luminaire is a lighting device, but it also requires suitable mounting and electrical connections. Similarly, an MCB is a protective device rather than simply a decorative electrical accessory.

1. Electrical Switches

Electrical switches control the flow of electricity to lighting circuits or compatible equipment. They are among the most frequently used electrical fittings in residential, commercial and institutional buildings.

Types of Electrical Switches

One-way switch: Controls a lighting circuit from one location. It is commonly used in small rooms, utility areas and individual spaces.

Two-way switching arrangement: Allows the same light to be controlled from two locations. It is useful in staircases, corridors and rooms with more than one entrance. The term describes the switching arrangement; the actual switch terminology can vary by market.

Intermediate switching arrangement: Allows a light to be controlled from three or more locations when used with suitable switching devices. It can be useful in long corridors and larger circulation areas.

Dimmer switch: Adjusts light output when paired with compatible lamps or luminaires. Dimming compatibility, minimum load and control method should be checked before specification.

Push-button switch: Operates through a momentary push mechanism. Depending on the system, it may be used with relays, timers or automated lighting controls.

Fan regulator: Controls the speed of compatible fans. The regulator must match the fan motor and the intended control technology.

Smart switch: Provides automated or remote switching through a compatible control system. Network requirements, control protocols, commissioning and manual override should be considered.

Architectural considerations for switches

Switch locations should be coordinated with room entrances, door swings, furniture and the intended lighting-control strategy. A switch placed behind a door or a fixed cupboard may be inconvenient even if its position appears reasonable on the electrical drawing.

For bedrooms, consider access from the entrance and the bed where appropriate. In staircases and long corridors, provide suitable control arrangements at the relevant circulation points. For accessible public buildings, consider reach ranges, operating force, contrast and ease of identification.

Do not apply one mounting height to every building. Determine the final position from applicable accessibility provisions, project requirements, furniture layouts and the electrical design.

2. Socket-Outlets and Plugs

Socket-outlets provide points at which appliances and equipment can be connected to an electrical supply. Plugs are fitted to appliance cords or equipment leads and connect with compatible socket-outlets.

The outlet type, current rating, voltage, earthing arrangement and protective measures must be suitable for the intended equipment and installation.

Common types of socket-outlets

TypeTypical applicationDesign consideration
General-purpose outletLiving rooms, bedrooms and general-use areasCoordinate with furniture and likely appliance locations
Higher-rated outletAppliances with greater electrical demandConfirm circuit design and equipment requirements with the electrical consultant
Dedicated appliance outletAir conditioners, ovens, pumps or other specified equipmentCheck load, connection method, isolation and manufacturer’s instructions
Floor box outletOffices, meeting rooms and adaptable workspacesCoordinate with floor finishes, furniture, cleaning and access
Weather-resistant outletSuitable outdoor or exposed locationsSelect the correct enclosure and environmental protection
Industrial socket-outletWorkshops and industrial facilitiesCheck electrical rating, ingress protection and any required interlocking
Data or communication outletWorkstations, bedrooms and meeting roomsCoordinate with the relevant low-voltage system and cable route

A higher-rated outlet does not, by itself, make an installation suitable for a higher-load appliance. Cable sizing, circuit protection, wiring method, supply characteristics and the appliance’s requirements must all be checked.

Socket planning in residential buildings

In homes, socket positions should be established from a furniture and appliance layout rather than by distributing outlets at arbitrary intervals.

Living rooms: Coordinate outlets with television units, media equipment, seating, floor lamps and cleaning equipment.

Bedrooms: Consider bedside charging, desk arrangements, dressing tables and cleaning access.

Kitchens: Identify the intended positions of refrigerators, ovens, dishwashers, exhaust systems and countertop appliances. Coordinate outlets with cabinetry, splash zones and appliance connection requirements.

Bathrooms: Electrical equipment and outlets require particular attention to the applicable rules for the location, water exposure and protective measures. A general-purpose outlet should not be positioned simply because a convenient wall space is available.

Balconies and terraces: Consider weather exposure, cleaning practices and the suitability of the complete outlet assembly for its environment.

Accessibility and usability

The existing Archi-Monarch page discusses accessible positioning of switches and socket-outlets. Its numerical guidance should be checked against the standard and building requirements applicable to the project rather than copied as a universal rule.

For public buildings, accessible design should consider reach, approach space, obstructions, visibility, ease of operation and the needs of wheelchair users and people with limited dexterity.

3. Lighting Fittings and Luminaires

Lighting fittings provide the physical and electrical arrangement for producing and distributing light. The term luminaire generally refers to a complete lighting unit, including the components needed to distribute, position and protect its light source.

Common types of lighting fittings

Recessed luminaires: Installed within a ceiling or other suitable surface. They create a relatively unobtrusive appearance but require sufficient space, compatible construction and access for maintenance.

Surface-mounted luminaires: Fixed to a ceiling or wall surface. They are useful where a recessed installation is impractical or where the fitting itself forms part of the visual design.

Pendant luminaires: Suspended from a ceiling, often over dining tables, counters, reception desks or selected feature areas. Suspension height and circulation clearance should be coordinated with the room.

Wall-mounted luminaires: Used for general illumination, wayfinding, accent lighting and selected task applications. Their position should be coordinated with wall finishes, furniture and sightlines.

Track lighting: Uses adjustable luminaires mounted on a track. It can support flexible accent lighting in galleries, retail spaces and adaptable interiors.

Linear lighting: Provides elongated light distribution and can be surface-mounted, suspended or recessed. It is often used in offices, corridors, classrooms and contemporary interiors.

Emergency lighting and exit-sign luminaires: Support emergency egress and wayfinding where required by the applicable fire and building provisions. Their location and performance should be established through the project fire-safety strategy.

Lighting selection in architecture

Lighting design should respond to the activity performed in each space. The following factors are important:

  • Required illuminance and uniformity for the intended task.
  • Glare control and visual comfort.
  • Colour appearance and colour rendering where relevant.
  • Energy performance and compatibility with lighting controls.
  • Ceiling height, structural obstructions and service zones.
  • Maintenance access and replacement requirements.
  • Emergency lighting and other applicable safety requirements.

A decorative fitting is not automatically an appropriate primary light source. Likewise, a visually discreet luminaire may be unsuitable if it produces excessive glare or fails to provide sufficient illumination for the task.

4. Ceiling Roses and Lamp Holders

A ceiling rose is a fitting traditionally used to provide or cover the connection point for a suspended light fitting. Some designs incorporate terminals or cord-grip arrangements, while others are primarily decorative covers. The specific product construction and rating must be verified.

A lamp holder supports and electrically connects a compatible lamp. Its suitability depends on the lamp type, voltage, current, temperature and intended installation.

Design and installation considerations

  • Confirm that the fitting is rated for its intended electrical and mechanical duty.
  • Ensure suspended fittings are supported by an appropriate fixing or support system.
  • Coordinate pendant locations with ceiling finishes, ceiling voids and structural elements.
  • Avoid treating a decorative cover as a substitute for an appropriate electrical enclosure.
  • Provide access to connections and components that require maintenance.

Modern integrated LED luminaires may not use a replaceable lamp holder. In these cases, the manufacturer’s instructions determine the servicing and replacement method.

5. Junction Boxes and Mounting Boxes

Junction boxes house electrical connections or branches where the wiring system and applicable installation rules permit them. Mounting boxes provide a secure enclosure or fixing arrangement for switches, socket-outlets and similar devices.

These components may be concealed within walls, positioned above accessible ceilings, installed in suitable surface-mounted systems or provided as weather-resistant enclosures in exposed areas.

Important considerations

Accessibility: Connections that require inspection or maintenance must remain accessible as required by the applicable rules. Concealing a junction box behind a permanent finish can make future maintenance difficult and may be impermissible for the specific installation.

Enclosure suitability: The box material, construction and ingress protection should be suitable for its location and exposure.

Space and fill: The enclosure must accommodate the intended conductors, terminals and cable entries without unsafe crowding.

Fire and acoustic performance: Wall and floor penetrations may require appropriate sealing or fire-stopping to maintain the performance of the building assembly.

Finish coordination: Flush boxes should be coordinated with wall thickness, plaster, tiles, joinery and final cover-plate dimensions.

6. Conduits and Cable Management Accessories

Conduits, cable trays, trunking and their associated fittings help route and manage electrical cables. The appropriate system depends on the cable type, installation environment, mechanical protection required, support arrangement and applicable electrical standards.

Common cable-management components

  • Conduit: A protective route for suitable electrical conductors or cables.
  • Conduit bends and elbows: Change the direction of a conduit route.
  • Couplers: Join compatible conduit lengths or system components.
  • Adaptors and bushes: Provide compatible transitions or protect cable entries where required.
  • Junction and draw-in boxes: Provide permitted connection points or access for cable installation.
  • Cable glands: Secure and seal cable entries into compatible equipment or enclosures.
  • Cable trays and ladders: Support cable routes in suitable building-service spaces.
  • Trunking: Provides an enclosure for organized cable distribution.
  • Clips and supports: Secure cables or cable-management systems to the building fabric.

Architectural coordination

Cable routes should be coordinated with structural beams, slabs, ceiling systems, plumbing, HVAC ducts and fire-protection services. The design team should identify service zones and agreed crossing points before construction.

Avoid drilling, cutting or forming openings through structural members without the necessary approval from the structural engineer. The electrical consultant should establish the appropriate wiring method and cable sizing; the architect should coordinate space, access and finish integration.

Where electrical services pass through fire-rated walls or floors, the penetrations and associated sealing system must maintain the required fire performance.

7. Electrical Distribution and Protective Devices

Protective devices are essential to the safe operation of a building’s electrical installation. They are related to electrical fittings and accessories, but their primary purpose is circuit protection and safe isolation rather than ordinary user connection.

Main protective devices

DevicePrimary functionImportant distinction
MCB — Miniature Circuit BreakerProtects a circuit against specified overcurrent conditions, including overload and short circuitSelection depends on the circuit and design requirements
RCCB/RCD — Residual-Current DeviceDetects residual current under specified conditions and disconnects the circuitDoes not by itself provide comprehensive overload and short-circuit protection
RCBO — Residual-Current Circuit Breaker with Overcurrent ProtectionCombines residual-current and overcurrent protection functionsMust be selected for the intended circuit and installation
FuseInterrupts a circuit when its fusible element operates under specified conditionsRequires the correct type and rating
SPD — Surge Protective DeviceLimits specified transient overvoltages and diverts associated surge currentSelection and coordination depend on the installation and risk assessment
Isolator or disconnecting deviceProvides an appropriate means of isolation where designed for that functionIts switching and fault-interruption capabilities must not be assumed

These devices are not interchangeable. The electrical designer must determine the protection arrangement, ratings, coordination and disconnection requirements for the installation.

In India, consult the applicable provisions of the National Electrical Code of India, relevant Indian Standards and current Central Electricity Authority regulations. The CEA maintains a regulations page that includes the 2023 safety regulations and a 2026 amendment; the applicable consolidated requirements should be checked for the project.

Central Electricity Authority

+2

Architectural implications

Electrical distribution boards and associated equipment require planned locations, suitable working space, appropriate access, environmental protection and coordination with other services. Their enclosure and location should follow the equipment manufacturer’s instructions and applicable installation requirements.

For larger equipment, plant rooms and electrical-service spaces, refer to the separate Archi-Monarch article on Placement of Electrical Equipment in Buildings.

8. Earthing and Bonding Accessories

Earthing and protective bonding are parts of the electrical safety system, not merely optional accessories.

Protective conductors, earth terminals, bonding connections and related components help implement the protective arrangements specified for the installation. Their function is different from that of an ordinary neutral conductor.

The precise arrangement depends on the supply system, equipment, installation design and applicable standards.

Key considerations

  • Ensure that protective connections are specified and installed according to the approved electrical design.
  • Use compatible components and appropriate terminals.
  • Do not remove or bypass protective conductors to resolve a nuisance trip or other operational problem.
  • Ensure that accessible metal parts are treated according to the applicable protective measures.
  • Have continuity and other required tests carried out by qualified personnel.

For Indian projects, IS 3043:2018 is an important reference for the code of practice for earthing, subject to checking for applicable revisions and amendments.

Bureau of Indian Standards

+1

9. Sensors, Timers and Smart Electrical Accessories

Modern buildings may use control accessories to improve convenience, manage lighting operation and integrate building systems.

Occupancy and presence sensors operate compatible lighting or control systems based on detected movement or presence. They can be useful in circulation areas, washrooms, meeting rooms and selected service spaces.

Timers switch compatible circuits according to a programmed schedule.

Photocell controls respond to ambient light levels and can be used in appropriate outdoor lighting arrangements.

Smart switches and controllers may support remote operation, scenes, scheduling and integration with a building automation system.

Thermostats and compatible control interfaces manage heating or cooling equipment rather than acting as ordinary lighting switches.

When specifying these systems, consider control compatibility, power requirements, wiring topology, network connectivity, commissioning, user privacy where relevant and the consequences of control-system failure.

Automation should improve usability and operational performance without compromising the safe operation of essential building systems.

10. Electrical Fittings for Different Building Types

The appropriate fitting schedule depends on the use, occupancy, environmental conditions and equipment of the building.

Building typeTypical componentsPrincipal planning priorities
ResidentialModular switches, general-purpose outlets, luminaires, fan controlsFurniture, appliances, convenience and future flexibility
OfficesSwitches, task-lighting controls, workstation outlets, floor boxes and data pointsDesk layouts, power and data coordination, adaptability
Educational buildingsLighting controls, general-purpose outlets and specialist equipment connectionsUser safety, supervised use, robust installation and maintenance
Healthcare buildingsGeneral and specialist outlets, task lighting, essential-system interfaces where specifiedClinical risk, continuity of supply, equipment compatibility and applicable healthcare requirements
Hotels and hospitalityBedside controls, room controls, outlets, decorative and functional lightingGuest convenience, maintainability and coordination with joinery
Retail buildingsTrack lighting, display lighting, general outlets and equipment connectionsFlexible displays, glare control, changing layouts and safe access
Industrial buildingsIndustrial outlets, suitable enclosures, isolators and cable-management systemsElectrical load, mechanical damage, dust, moisture and any hazardous-area classification
Outdoor and landscape areasSuitable outdoor luminaires, weather-resistant outlets and control equipmentExposure, ingress protection, corrosion, maintenance and public safety

These are typical examples, not universal schedules. Specialist buildings require a project-specific electrical design.

11. Planning Electrical Fittings in Architectural Drawings

Electrical fittings should be coordinated with the architectural layout before the final finishes and construction details are fixed.

Step 1: Understand the space and its use

Review the room’s function, occupancy, furniture, appliances, equipment and anticipated changes in use. A bedroom, laboratory, commercial kitchen and open-plan office require different fitting schedules.

Step 2: Prepare a coordinated furniture layout

Identify beds, desks, wardrobes, kitchen counters, television units, fixed equipment and other elements that influence fitting locations.

Step 3: Develop the electrical layout

The electrical consultant establishes the circuit arrangement, switching strategy, outlet requirements, loads, wiring routes and protective measures. The architectural drawing should communicate the agreed locations and coordination requirements clearly.

Step 4: Coordinate wall and ceiling details

Check switch plates, outlet boxes, luminaires, suspended ceilings, access panels, structural elements, joinery and finish thicknesses.

Step 5: Review accessibility and safety

Check relevant accessibility requirements, wet-area conditions, equipment clearances, maintenance access and applicable electrical and fire-safety provisions.

Step 6: Coordinate with other MEP services

Review electrical routes against HVAC ducts, plumbing lines, drainage, firefighting systems and other services. Resolve conflicts before issuing coordinated construction drawings.

Step 7: Verify the installation before finishes

Confirm agreed locations, box depths, conduit routes, sleeves, supports and approved penetrations before plastering, ceiling closure or other irreversible work.

Step 8: Inspect and document

The electrical contractor and responsible professionals should complete the specified inspections, tests, commissioning and documentation before the installation is put into service.

This workflow reduces rework and helps preserve the intended architectural design.

12. Electrical Fittings and Accessories: Materials and Finishes

The material of a fitting influences its appearance, durability, environmental suitability and maintenance.

Material or finishTypical useSelection considerations
ThermoplasticSwitch plates, mounting components and selected enclosuresProduct rating, heat performance, impact resistance and intended use
MetalSelected plates, enclosures and industrial fittingsCorrosion resistance, earthing arrangements and suitability for the environment
Stainless steelSelected specialist plates and enclosuresGrade, corrosion exposure, cleaning requirements and compatibility
Glass or decorative finishesSelected switch plates and control interfacesImpact resistance, cleaning and manufacturer’s limitations
CeramicSelected insulating or specialist componentsProduct-specific ratings and suitability for the installation
Weather-resistant polymers or metalsSuitable outdoor fittings and enclosuresUV exposure, temperature, water ingress, corrosion and mechanical damage

Do not select a material based on appearance alone. The complete product must be appropriate for its electrical duty and installation environment.

Coordination with interior design

Architects and interior designers can coordinate switch plates and visible fittings with door hardware, wall panels, joinery and decorative finishes. However, a visually consistent range should not be achieved at the expense of safe ratings, accessibility, durability or maintainability.

Where several accessory types are used in the same room, confirm their dimensions, plate arrangements, mounting requirements and compatibility before procurement.

13. Safety and Selection Considerations

Electrical accessories should be selected by qualified professionals in accordance with the electrical design and the applicable standards and regulations.

Important selection criteria

  • Rated voltage and current.
  • Intended circuit and connected load.
  • Compatibility with the wiring system and protective devices.
  • Appropriate earthing and insulation arrangements.
  • Environmental conditions, including moisture, dust, temperature and corrosion.
  • Mechanical durability and mounting requirements.
  • Required ingress protection for the installation location.
  • Compatibility with connected appliances and control systems.
  • Availability of replacement parts and maintenance instructions.
  • Applicable product certification and standards.

Wet areas and outdoor locations

Bathrooms, kitchens, balconies, terraces, washdown areas and other exposed locations require careful assessment of water exposure and environmental conditions.

The required protection depends on the actual location and applicable rules. An IP rating alone does not establish that an accessory is safe for every wet location, nor does it replace required circuit protection, earthing or installation measures.

Electrical work and testing

Installation, alteration and testing should be undertaken by appropriately qualified personnel. Before energization, the specified checks should verify the installation’s conformity with the approved design and applicable requirements.

The Central Electricity Authority publishes safety regulations and amendments through its official website. The relevant current provisions should be consulted rather than relying solely on older web articles or generic product descriptions.

Central Electricity Authority

+1

14. Advantages of Properly Selected Electrical Fittings

Properly specified and coordinated fittings can provide several benefits:

  1. Convenience: Controls and outlets are located where users need them.
  2. Safety: Suitable components support the electrical design’s protective measures.
  3. Better interiors: Fittings integrate with wall finishes, ceilings and furniture.
  4. Improved maintenance: Accessible and compatible components simplify inspection and replacement.
  5. Greater adaptability: A well-planned arrangement can accommodate changes in furniture and equipment.
  6. Better coordination: Early agreement between architectural and electrical teams reduces avoidable site conflicts.
  7. Operational efficiency: Suitable lighting controls and compatible accessories can support more effective use of energy.

These benefits depend on appropriate design, installation, operation and maintenance. A premium-looking accessory does not automatically deliver better safety or energy performance.

15. Common Mistakes in Electrical Fittings Planning

MistakeWhy it causes problemsRecommended approach
Placing outlets before furniture planningOutlets may become inaccessible or poorly positionedCoordinate with the furniture and equipment layout
Ignoring door swingsSwitches may be obstructed by open doorsReview door clearances and entry sequences
Using unsuitable fittings in exposed locationsMoisture, dust or corrosion may affect the installationVerify the environmental rating and installation requirements
Confusing MCBs with RCDsDifferent protection functions may be overlookedSpecify the required protection arrangement through the electrical design
Concealing maintenance pointsInspection and repair become difficultMaintain the required access to serviceable components
Failing to coordinate ceiling fittingsConflicts can occur with beams, ducts and access panelsCoordinate reflected ceiling and MEP drawings
Cutting structural members for cable routes without approvalMay compromise structural performanceObtain the structural engineer’s approval for any proposed penetration
Selecting decorative accessories without checking ratingsAppearance may take priority over suitabilityVerify product data, ratings and applicable standards
Assuming one mounting height fits every roomUsability and accessibility requirements varyEstablish positions for the intended users and project requirements
Ignoring future equipment needsExtensions and modifications may become costlyDiscuss foreseeable loads and flexibility with the electrical consultant

16. Practical Checklist for Architects

Before finalizing the electrical layout, review the following items with the electrical consultant.

[ ] Room-by-room switch and socket schedule coordinated with furniture
[ ] Lighting locations coordinated with the reflected ceiling plan
[ ] Door swings, circulation and accessible operating positions checked
[ ] Appliance connections and equipment requirements identified
[ ] Wet-area and outdoor fittings assessed for their environment
[ ] Electrical distribution and protection requirements coordinated
[ ] Conduits, sleeves and cable routes coordinated with structure and other MEP services
[ ] Fire-rated penetrations and access requirements reviewed
[ ] Fitting finishes, mounting depths and dimensions coordinated with interiors
[ ] Testing, inspection and maintenance access included in project documentation

This checklist is a coordination aid, not a substitute for electrical design, statutory approval or professional inspection.

17. Conclusion

Electrical fittings and accessories are small but essential parts of a building’s electrical installation. Switches, socket-outlets, lighting fittings, mounting boxes, cable-management components and protective devices each serve distinct purposes, and their suitability depends on the building’s use and the requirements of the electrical system.

For architects, the main challenge is to coordinate these components with space planning, furniture, finishes, accessibility, structural elements and other building services. Early collaboration with the electrical consultant helps prevent clashes, improve usability and support safe, maintainable installations.

For Indian projects, technical decisions should be based on the applicable edition of the National Electrical Code of India, relevant Indian Standards, current CEA regulations and approved project documentation. Product selection and installation should be verified by appropriately qualified professionals.